Electrical supply sizing

HEDNO low-voltage supply categories, with the rated current of each and the feeder and protection we would normally fit between the meter and the main panel.

V

Enter the demand in kVA, kW or amps to find the smallest supply that covers it.

Supply

> 250 kVA

This needs a medium-voltage connection or a dedicated arrangement with HEDNO.

Supply

Supply cable
Meter–panel feeder
Meter fuse
Panel main fuse
    All supplies in the table
    Result

    All low-voltage supplies

    Feeder sizes in mm² copper. Supply cable is HEDNO's side of the meter.
    Supply kVA I (A) Supply cable Meter–panel feeder Meter fuse Panel main fuse
    Single-phase 230 V
    No 03 8 34.8 2×6 3×10 35 A (or MCB 40 A) 35 A
    No 05 12 52.2 2×16 3×16 63 A 50 A
    Three-phase 400 V
    No 1 15 21.7 4×6 5×10 3×25 A 3×25 A
    No 2 25 36.1 4×6 5×10 3×35 A (or MCB 3×40 A) 3×35 A
    No 3 35 50.5 4×16 5×16 3×63 A 3×50 A
    No 4 55 79.4 4×25 3×25 + 16 + 16 3×100 A 3×80 A
    No 5 85 122.7 4×50 3×50 + 25 + 25 3×160 A 3×125 A
    No 6 135 194.9 1×95 single-core 3×120 + 70 + 70 3×250 A 3×200 A
    No 7 250 360.8 1×150 single-core 3×240 + 120 + 120 3×400 A 3×350 A

    Before you use these numbers

    • Categories and ratings are HEDNO's. HEDNO confirms the category when you apply; above 250 kVA the connection moves to medium voltage or a dedicated arrangement.
    • Current is calculated as S/230 for single-phase and S/(√3·400) for three-phase supplies.
    • Feeder sizes assume a short run of PVC-insulated copper cable fixed on a surface (reference method C). In conduit, grouped with other circuits, in a hot space or over a long distance, size the cable to ΕΛΟΤ HD 384: in conduit, for example, 3×25 and 3×50 fall below the 100 A and 160 A meter fuses that protect them. Check voltage drop for the actual length.
    • The reduced neutral from supply No 4 upwards is acceptable only where third-harmonic current is low. Buildings dominated by LED lighting, IT equipment or drives need a full-size neutral.
    • Where the meter and panel fuses have the same rating, as in No 1, the two will not discriminate. For gG fuses keep a ratio of at least 1.6:1 if selectivity matters.